KNX-USB
KNX-USB interface
The KNX-USB interface enables communication between the KNX bus and a computer for programming and monitoring devices on the bus by using the ETS program. Additionally, the interface can work in the bus logging mode, in which the history of events generated on the KNX bus is saved to the interface non-volatile memory (up to 350 000 events).
In the bus logging mode, the interface does not support communication with the ETS program.
Features:
- communication with the KNX bus via integrated bus connector
- power supply from the KNX bus or from the computer USB port
- galvanic isolation of the KNX system and computer
- data transmission between the interface and the computer acc. to USB 2.0 standard
- LEDs indicating the device status
- easy to connect and use
The actual appearance of the products may differ from the presented images. Product descriptions are provided in the web service for information purposes only.
Documentation
general information manual
updated: 2019-11-29
357 KB
Software
multi-language
compiled: 2017-09-07
Certificates
Other certificates
updated: 2020-01-28
168 KB
EU declaration of conformity
updated: 2024-06-11
116 KB
Technical Data
Maximum length of USB cable
5 m
Maximum power draw from KNX bus
0,6 W
Maximum power draw from USB
0,3 W
KNX bus voltage
20…30 V DC
Current draw from KNX bus
< 20 mA
Current draw from USB
< 30 mA
Enclosure dimensions
67 x 34 x 21 mm
Temperature range for storage / transport
-25°C...+70°C
Operating temperature range
-5°C...+45°C
Information materials
1catalogue
2leaflet - end user
3leaflet - installer
4technical data
5product data sheet