WZ-400

Addressable remote indicator

The WZ-400 indicator is used to indicate the selected events in the fire alarm system by LEDs. The events may involve:

  • a single detector / a single side line module:
    • alarm triggered by detector / module
    • faulty detector / module
    • disabled detector / module
  • zones:
    • alarm in zone
    • faulty device in zone
    • disabled device in zone
  • groups:
    • activation of group sounders
    • faulty device in group
    • disabled device in group

The indicator is designed to operate in the detection line of the ACSP-402 addressable fire alarm control panel.

  • optical signaling by LEDs
  • signaling controlled by the control panel:
    • capability to link the indicator with a single detector, a single side line module, zone or group
    • selection of events to be indicated
  • double-sided short-circuit isolator
  • powered from the detection line
WZ-400
The actual appearance of the products may differ from the presented images. Product descriptions are provided in the web service for information purposes only.

Documentation

general information manual
updated: 2023-03-14
172 KB
mounting template
updated: 2023-03-06
118 KB

Certificates

Other certificates
updated: 2023-03-15
1.31 MB
Declaration of performance
updated: 2024-03-01
429 KB
EU declaration of conformity
updated: 2024-06-19
115 KB

Technical Data

Enclosure dimensions
84 x 84 x 30 mm
Operating temperature range
-10°C...+55°C
Weight
56 g
Maximum humidity
93±3%
Current draw when detecting
200 µA
Current draw when emitting an alarm
1,4 mA
Power supply voltage
18...26 V DC
Event signalling (fire alarm)
świecenie ciągłe
Event signalling (disabled device)
wolne miganie (0,91 Hz)
Event signalling (faulty device)
szybkie miganie (3,65 Hz)

Information materials

3leaflet - installer

5product data sheet

 © 1990-2021 SATEL sp. z o.o.
legal | privacy policy | Feedback | about site

The Satel.pl website uses cookies to enable Users' to take advantage of Satel.pl features as well as for statistical purposes. Unless you block cookies, you grant your consent for their use and storage in device memory. You must remember that you are able to manage cookies by means of your browser settings. Lack of adjustment of these settings means your consent for the Satel.pl website to use the cookies. See our Privacy Policy for more information.